Little known facts about tan delta/power factor testing

Pylons in dresses!

Putting electric vehicles to the test

Q&A


Little known facts about tan delta/power factor testing
Dinesh Chhajer, Technical Support Group

Pylons in dresses!

For many engineers, the transmission towers that span the countryside are works of art in their own right, but for installation artist Elena Paroucheva, who lives and works in France, these towers were just the beginning. In her work, Elena searches for connections between art, energy and the environment, and she saw that transmission towers provided her with, in effect, a blank canvas that she could use to develop and display these ideas.

Accordingly, she entered into discussions with RTE, the organisation responsible for the French electricity transmission network, and after two years of negotiation, she was granted permission to transform the appearance of four high-voltage transmission towers on the 225 kV line between the French cities of Amnéville and Montois. RTE also sponsored and supervised her work.

Before Elena’s ideas could be translated into reality, however, eighteen months of study were needed for, among other things, technical validation of the proposed methods for transforming the towers and the selection of suitable materials that would ensure the sustainability and resistance to degradation of the installations.





Examples of Elena Paroucheva’s work

Ultimately Elena Paroucheva started work on her metamorphosis of the transmission towers in August 2001 and completed it by December 2003. The project was no minor undertaking – in total it used 3,284 m of steel cable, 2,708 m of stays, 525 m of plastic canvas, 576 m of steel tube and 40 light projectors that are controlled via a satellite communications link.

The title of the project is -
Source – A Monumental Artwork” and the themes for the four transmission towers are “Source – Light”, “Source – Water”, “Source – Energy” and “Source – Flame”. As the pictures accompanying this article show, the results she has achieved are both inspirational and impressive.

For this project, which has been much admired by the public in general and by the art world, Elena has received widespread recognition, including most recently the laureate award for Science and Technology in European Art in a competition organised by SUPELEC within the framework of the French Presidency of the European Union.

Much more information about Elena Paroucheva’s unique “Source” project can be found on her website at www.art-elena.com, and there can certainly be no doubt that she has made her own rather special contribution to the art of power transmission!

With an increasing failure rate of substation electrical equipment, utilities and heavy industry must focus on preventive and predictive maintenance to ensure power system integrity and reliability. Electrical insulation is a common reason for electrical equipment failures and tan delta/dissipation/power factor (PF) testing is a popular way of diagnosing and estimating the condition of insulation as it ages. There are, however, a number of issues relating to PF testing that are not nearly as widely understood as they should be.

DELTA4000 performs automated power factor tests at up to 12 kV

PF testing is widely used on electrical equipment such as power transformers, circuit breakers, generators and cables. PF values, trended over time, can help in detecting problems like contamination, high moisture content and the presence of voids in insulation. Excitation current tests, along with PF tests, performed on power transformers, can also help in detecting turn-to-turn insulation failure.

Dissipation/Power Factor vs. Voltage
Dissipation factor tests are usually performed at 10 kV or the readings are converted to 10 kV equivalent. The best voltage for PF tests is a frequently debated topic as instruments are now available that allow the tests to be performed at voltages from 27 V to 12 kV. What test voltage is “good enough” for accurate and reliable measurements? The answer depends on the type of test specimen and the test conditions.

Most power transformers have oil-paper type insulating systems that exhibit a flat response when PF is measured as a function of test voltage. However, motors and generators typically have dry or solid insulation whose PF values may vary with test voltage. Values increase with increasing test voltage due to the voids that are almost invariably present in solid insulation. The increase in PF value as a function of voltage corresponds to increasing ionization in the voids.

One reason that industry has standardized on a 10 kV test voltage is for immunity against electrostatic interference; power transformers operating in HV substations are subject to a lot of electrical noise and interference. An HV test signal provides better signal to noise ratio, giving more accurate measurements. Test instruments with very high noise suppression capability are required for measurements in HV substations as the test current is very low in insulation tests and noise levels can be as high as 20 times the test current.

Negative Power Factor Values
For perfect insulation, the PF should be zero. In practice, any value close to zero is considered to indicate a good insulation system. PF test sets always try to measure a single capacitor, but if the test object has some phantom circuits along with that single capacitance, the results look strange.

For example, when performing tests on bushings, three-winding transformers or inter-phase insulation of rotating machinery, the PF values will sometimes be negative. PF is a measure of watts loss in the insulation.

Negative PF therefore corresponds to watts generation. Obviously, insulation cannot generate power, which shows that negative PF values are not real but instead tell us that the insulation does not behave as an expected capacitance.

Figure 1: Specimen in UST mode with surface loss components

Negative values also appear with some specimens that have high surface leakage. As shown in Fig 1, phantom circuits introduce a current (Is) which changes the phase angle of the measured test current (IT). The surface loss current (Is) is predominantly resistive (Rs) and has a very small phase angle with respect to the applied voltage. Capacitive coupling (Cc) may be present as a result of this parallel path of Rs to main insulation under test.

1

Fig 2: Vector diagrams with different Is phase angles and different magnitude of INET


Smaller phase angles for surface loss current (Is) can lead to negative PF values. Measured test current (IT) is the vector difference of total current (INET) and surface loss current (Is). In UST or GST configurations, this surface loss makes the measured test current (IT) phase angle greater than 90º, and this results in negative PF values.

It is important to understand where negative PF values come from. For some specimens it is just a result of design – for example, the presence of electrostatic grounded shield between the inter-windings of a transformer. In other cases, where negative values are encountered users should consider eliminating all external effects by following best testing practices such as verifying proper grounding circuits, cleaning external bushing surfaces, avoiding unfavorable weather conditions and using guard circuits effectively. Repeated negative values after taking these precautions could point toward contamination or a bad insulation system.

Excitation Current vs. Voltage
Excitation current testing is commonly performed along with PF testing. It is a voltage dependent test and is always performed in UST mode. Like PF tests, the excitation current readings are normalized to 10 kV equivalent values, using a linear approximation. When dealing with specimens that are highly inductive, such as power transformers, the relationship between voltage and current is, however, not linear.

Assuming a linear relation to determine 10 kV equivalent excitation gives only approximate values. It is, therefore, important to perform tests at the same voltage if excitation current historical data needs to be trended. Tests performed at different voltages and then corrected to 10 kV may not be comparable. This is important as trending data is critical when evaluating problems with turn-to-turn insulation.

2

Figure 3: Excitation current measurement on a Delta winding with third leg grounded


When performing excitation current measurements on delta windings, it is important to ground the third leg of the delta configuration as shown in Fig 3. Since excitation current is a UST test, grounding the third leg eliminates the current flowing in the other two windings from the measurement circuit.

Depending on the inductance and resistance of each winding, if third leg is not grounded the results would be approximately 30% to 50% higher than true readings.

A transformer with magnetized core can exhibit higher excitation current measurements than normal. IEEE 62-1995 section 6.1.3.4 states, “If a significant change in the test results is observed, the only reliable method of excluding the effect of residual magnetism is to demagnetize the transformer core.” The factors discussed here that affect excitation current measurements should be borne in mind before performing the test.

Temperature Correction Factors for PF readings
The dissipation factor values are highly dependent on temperature. IEEE C57.12.90 section 10.10.4 Note 3 (b) states that “Experience has shown that the variation in power factor with temperature is substantial and erratic so that no single correction curve will fit all cases.” Nevertheless, correction factor tables have traditionally been used to bring all data to a common base of 20 °C. It is imperative only to compare a specimen’s PF values that are taken at a similar temperature or corrected to the same temperature accurately. For different specimens, changes in temperature affect PF values in different ways. And even the same specimen will become more temperature dependent as it ages. Temperature correction factors are highly dependent on insulating material, its structure, ageing, presence of moisture or contamination and other influences. However, temperature correction data is based upon the average values. Since each test object is unique, using these average corrections introduces errors.

New transformers have relatively weak temperature dependence and the use of standard tables overcompensates. As the object ages, same average correction factors would under compensate and error pre- dominates in the other direction. Trending of PF values becomes more critical in the second half of the life cycle. In this second half, correction factors should be larger because of the increased effect of temperature on the insulation.

Using average factors can lead to incorrect trending and inaccurate estimation of the remaining healthy life of the object. IEEE Standard 62-1995 states, “Testing at temperatures below freezing should be avoided, since this could significantly affect the measurement.

Among the primary reasons for performing this test is the capability of detecting moisture in insulation. The electrical characteristics of ice and water are quite different and it is much more difficult to detect the presence of ice than it is to detect water; sometimes it is impossible. ”Measuring PF at too high or too low a temperature can introduce errors, and the IEEE recommends performing PF tests at or near
20 °C.

However, it’s not always practical to cool down or heat up the test specimen to 20 °C. Fortunately, new technology makes it possible to accurately correct PF values to 20 °C without resorting to correction factor tables based on averages. Using dielectric frequency response (DFR), the unique temperature correction factor of each test object can be determined. This is possible because a PF measurement at a certain temperature and frequency corresponds to a PF measurement made at different temperature and frequency. Therefore by measuring PF at different frequencies, it is possible to determine the temperature dependence of the specific test object. With this technique,
PF can be measured at any insulation temperature
[5 °C – 50 °C] and then corrected to 20 °C accurately and precisely.

Conclusion
Electric apparatus has failed and will continue to fail because of insulation deterioration. A proactive approach is the key to monitoring the integrity of the insulation system and preventing or at least anticipating such failures. Tan delta/power factor diagnostic testing is an important tool in determining the quality of the insulation and estimating its remaining healthy life.

Dissipation factor readings are dependent on various factors and it is important to be aware of these. Test voltage, electrostatic interference, temperature, humidity, surface losses and other parameters can greatly influence PF measurements. A better understanding of the impact of these parameters will help in obtaining accurate measurements that can be relied upon in the decision making process.


Putting electric vehicles to the test
Dave Moore, Product Manager

In this issue, Megger’s technical support group experts tackle some rather general but surprisingly common questions relating to installation testing in commercial and industrial buildings.

Q: In addition to performing tests on power systems, my team and I are often asked to carry out routine tests on ordinary building electrical installations, so what’s the best type of instrument to use?

A: Although some engineers who regular carry out installation testing prefer to use separate instruments for each of the main tests involved, the most popular solution is a multifunction tester. This provides, in a single instrument, facilities for all of the tests needed to certify an installation in line with current regulations. Modern multifunction testers are compact, dependable and easy to use.

Q: Apart from the features routinely needed for installation testing, do multifunction instruments typically offer an “extras” that might be useful?

A: Almost all will offer facilities for measuring voltages and some for checking supply frequency. The latest models, however, like Megger’s new MFT1730, can also be used to measure earth electrode resistance. This is an increasingly common requirement in photovoltaic and other types of “green” energy systems and, indeed, in power installations. Another useful feature provided by some multifunction instruments is internal results storage, with facilities for Bluetooth wireless download to a laptop computer or even a smartphone. The best units of this type are complemented by software that automatically fills in the test certificates as the results are received by the laptop or smartphone. This saves a lot of time as well as eliminating the errors that are almost inevitable when the certificates are filled out by hand.

Photo: Bosch

As concern continues to grow over the environmental impact of vehicles with conventional petrol engines, the popularity of electric and hybrid vehicles is increasing rapidly. In fact, it has been reported that vehicles with hybrid drives already make up 2% of new registrations worldwide, and that this figure is expected to reach at least 7% in the next five years.

This is good news for the environment, but it does create challenges for the garages and service agents that will be called upon to maintain these new vehicles. In particular, they will have to deal with electrical systems that work at much higher voltages than those found on traditional vehicles. One important consequence is that, in order to ensure safety and reliability, insulation testing will be a prime requirement, in much the same way that it currently is for electrical installations in buildings.

In the fullness of time, standards will undoubtedly be developed for insulation testing on vehicles but, for the present, there are none. That doesn’t mean, however, that there are no instruments available. On the contrary, a huge range of insulation testers is currently available, so the problem is more likely to be choosing the best option for vehicle applications.

With this in mind, it’s worth looking at the characteristics that are desirable in insulation testers for use on electric vehicles. High voltage types – instruments that test at 5 kV or above – are not necessary. While they have advantages in some applications, for example with large railway traction motors, they are not needed for the current generation of road vehicles.

Much more appropriate are handheld insulation testers that work at 1 kV. What is important, however, is that the instrument should have a high maximum reading. There’s a lot of difference between a tester that shows infinity for everything over, say, 1 GΩ, and one that gives dependable readings up to 200 GΩ, because the latter provides much more information about faults that may be developing, but have not yet reached a critical stage.

Also important is support for diagnostic insulation tests, such as Polarisation Index (PI) and Dielectric Absorption Ratio (DAR). At present, these tests are not widely used in connection with electric vehicles but, when performed regularly and the results logged over time, they can provide useful additional information about the life expectancy of wound components like motors. The information these tests provide is particularly useful in applications where there is a risk of moisture ingress and carbon deposits, as there invariably is with the drive trains of electric vehicles.

Internal storage of test results and facilities for downloading these results for inclusion in reports are other highly desirable features, since not only do they save time, they also eliminate the risk of errors that is always present when results are recorded manually. While result down-loading via a USB cable or similar is satisfactory, there is a lot to be said for instruments that offer the added convenience of Bluetooth® wireless data transfer.

The physical characteristics of the instrument are also important. For regular use it needs to be small and light, and it should ideally allow one-handed operation.

It should have a large clear display, and the provision of an analogue arc alongside the usual digital readout is a distinct advantage, as the behaviour of the analogue display can provide useful extra information when performing insulation tests.

Finally, the ideal insulation tester for electric vehicle applications needs to be robust, and to have a good ingress protection rating – say IP54 – as garages and vehicle service centres can be tough operating environments.

1

Instruments that meet all of these criteria are available today – products in Megger’s MIT400 range being good examples – and it is worth bearing in mind that they will not only fulfil the requirements of those called upon to test electric and hybrid vehicles, but will also find many applications in testing the charging stations associated with these vehicles.