Free Phone: 0800 485 990 (NZ)

Outram PQ Analyser Quick Comparison Chart

  [PM7000] Power Quality Analyser

PM7000

[PM4000] Power Quality Analyser

PM4000

[PM3000] Power Quality Analyser

PM3000

[PM1000] Power Quality Analyser

PM1000

No. Voltage Channels

4 4 3 1

Voltage Range AC

0-600Vrms or 0-1000Vrms (L-L and L-N). 0-848Vpk or 0-1414Vpk Transient voltages up to 4000V 0-600Vrms or 0-1000Vrms (L-L and L-N). 0-848Vpk or 0-1414Vpk Transient voltages up to 4000V 0-480Vrms or 0-600Vrms 0-678Vpk or 0-848Vpk 0-270 Vrms 0-381Vpk

Voltage Range DC

    0-480Vdc  

No. Current Channels

4 4 3 1

Current Range AC

0-400.0A or 0-6000A 0-400.0A or 0-6000A 0-50.00A, 0-400.0A or 0-3000A 0-50.00A or 0-1000A

Current Range DC

    Variable with relevant current clamps  

Ability to Measure Neutral

Differential Voltage Channels

 

Detailed Recording Channels

32 32 16 16

General Parameters

     

DC Measurement

    Optional  

Fault Level

Optional      

Flicker (Plt, Pst, Pinst, Pflag)

Highest order of individual harmonics

50th (127th Optional) 50th (127th Optional) 15th 15th

Interharmonics

Optional      

THD and THC

kW

KVA

KVAR

Power Factor

Unbalance (V & I)

Frequency 45-65Hz (Can automatically detect 50 or 60Hz nominal)

InRush Current

K Factor

   

Symmetrical Components

 

Single Cycle Adaptive Store

Data logging time interval single cycle to 12hrs or Auto-variable with Adaptive Store

Sag / Swell / Outage Monitoring

High Speed Waveforms with AutoRanking Waveform Capture

Yes at 19.2k, 153.6k, 1.2M Samples/sec Yes at 19.2k Samples/sec    

Transient detection

Yes both cycle & sub cycle Yes both cycle & sub cycle Yes down to single cycle Yes down to single cycle

CBEMA / ANSI / ITIC curve plots

   

Onboard Display

     

Live Results

Using PMMeter PMWave or PMScreen Using PMMeter PMWave or PMScreen Using PMMeter PMWave or PMScreen Using PMMeter or PMScreen

Bluetooth

Ethernet

Optional      

USB or Infra-Red Communication

USB USB USB USB-C

Remote screen with PMScreen

Remote Communications via PMGateway

Time Synchronisation over mobile phone or PC

   

Memory storage for recorded data

128MB 32MB 8MB (16MB & 32MB Optional) 8MB (16MB & 32MB Optional)

Expandable Memory with a memory Stick or Hard Drive

   

Fifo mode

Self Powered (powered from Phase A)

Can be charged from the mains if necessary (12V DC charger unless otherwise specified)

Power Lead

Portable/Fixed

P P P P

Operating Temperature

-20 to 60°C -20 to 60°C -10 to 60°C -10 to 60°C

Safety Rating

600V CatIV, 1000V Cat III (Fuses removed) 600V CatIV, 1000V Cat III (Fuses removed) 600V Cat III 300V Cat III

IP Rating

IP65 IP65 IP51 IP40

Software

Pronto for Windows Pronto for Windows Pronto for Windows Pronto for Windows